Documentation Files:
8586-710-schematic.pdf Single-page schematic for high-true version of 8586-710 board. 8586-711-schematic.pdf Single-page schematic for low-true version of 8586-710 board. |
|
| Part # 8586-710 | Price: $ 195 | Product Status: Production   Qty in Stock: 0 |
|
| ||
|
Automation Displays' sixteen-point pulse/latch card uses screw
terminals for inputs and solder connections for outputs. The card
accepts momentary or maintained dry-contact inputs. The inputs are
latched so that indicators (not included) remain illuminated even if
the input clears. Field input wiring requires seventeen wires: a single wire for each input, and a single common wire. This common wire can be +24 volts DC (use the high-true board) or DC ground (use the low-true board). A common alarm output is provided to drive a sonalert or common alarm indicator. Inputs are provided for separate RESET and SILENCE switches. These two inputs, as well as the common-alarm output, can be jumpered between multiple 8586-710 boards for systems requiring more than sixteen points. The circuit operates on 24 volts DC. Please specify high-true or low-true inputs when ordering. The input signal polarity is also used to drive the indicators. For example, a low-true input will apply a low signal to the indicator to turn it on. The board size is 16.3 inches (414 mm) by 5 inches (127 mm). It requires approximately two inches (50.8 mm) of depth for mounting. A similar circuit (E769-50) with connectors for inputs and outputs is also available. |
||
|
Terms & Conditions $ 195 USD |
| 3533 N. White Ave. Eau Claire, WI 54703 715.834.9595 (voice) 715.834.9596 (fax) adi@adipanel.com | |